Mon - Fri 08:00 - 18:00 Sat - Sun closed

+38(067)626-01-80
(0)
  • Your shopping cart is empty!

WAGA SMART PARKING DOZOR - a system for monitoring and detecting violations Complex solutions

Engineering systems monitoring box

Appointment
The monitoring system of engineering systems is designed to collect information from various devices - power supply, air conditioning, DGU, security and fire alarm systems, digital temperature sensors and discrete flood sensors.

The principle of operation
The monitoring system allows you to survey discrete values ​​such as "dry contact", in the amount of 24 pcs. The obtained values ​​are displayed in the WEB-interface and participate in the formation of alarm messages, as well as duplicated on the original terminals of accidents.

This box allows you to configure the parameters via a local connection configuration software via the RS232 interface or remotely via the WEB-interface. The RS232 interface has a galvanic isolation and a built-in power supply of the galvanically isolated part.

Also, the monitoring unit polls the values ​​of digital temperature and flood sensors, which are connected to individual remote adapters that are part of the box. Remote adapters are connected to the box via an FTP 5E cable via the RS485 interface. Box monitoring allows you to poll up to 4 remote sensor polling adapters for 1 RS485 interface. The unit generates accidents if the temperature values ​​go beyond the permissible range (for example, "high temperature accident"), or when the flood sensors are triggered. The received accidents are displayed in the WEB-interface, and can be sent in the form of trap-messages in the format SNMP v2, 3, and also are duplicated on initial terminals of accidents.

The monitoring system allows you to connect 3 external phase control adapters in the 380V network. The connection is made via an FTP 5E cable via the RS485 interface. Each external phase control adapter transmits digital voltage values ​​for each of the phases in a three-phase 380V network. The received accidents are displayed in the WEB-interface, and can be sent in the form of trap-messages in the format SNMP v2, 3, and also are duplicated on initial terminals of accidents.

In addition, the monitoring controller allows you to survey the equipment on digital interfaces RS485 (4 pcs.), RS 232 (2 pcs.) And Ethernet (5 pcs.).

Address

149 Zelena St, building 8a, Lviv, Ukraine

Work Schedule

Mon - Fri 08:00 - 18:00 Sat - Sun closed

Email

Address

Адрес Германия, г. Берлин, Grossbeerenstrasse 46-52
Address
Lviv, Zelena street, 149, building 8a
Address
Kiev, st. Academician Krymsky, 4A, 02000
Call center